10
Timeout
TIMEOUT defines the action that will be taken when the timer counts to 00:00:00. The selections are
NO ACTN, HOLD, ALARM, SHDN. The default is NO ACTION. Set using the UP/DOWN keys.
IMEOUT
SELECTION
CONTROL
ACTION
MESSAGE DISPLAYED
BEEPER ACTION
NO ACTN
none
none
none
HOLD
COOKSET is set to
COOKHOLD value
TIMEOUT HOLD
200° F (or cook hold temp)
Is flashed continuously
until a key is pressed to
clear it.
Sounds once with the number
of beeps set by ALARM
BEEPS
ALARM
none
TIMEOUT ALARM
Is flashed continuously
until a key is pressed to
clear it.
Sounds continuously with
groups of beeps set by
ALARM BEEPS selection
until a key is pressed to clear
it.
SHDN
Turns the fan output
off
TIMEOUT SHDN
Is flashed continuously
until a key is pressed to
clear it.
Sounds continuously with
groups of beeps set by
ALARM BEEPS selection
until a key is pressed to clear
it.
Alarm Deviation Setpoint
If the temperature of the pit deviates above the setpoint by the alarm deviation setpoint, the alarm will
sound and the display will blink COOK TEMP HIGH and the temperature value.
If the temperature of the pit deviates below the setpoint by the alarm deviation setpoint, the alarm will
sound and the display will blink COOK TEMP LOW and the temperature value.
The alarm is only allowed once the temperature gets near the cook temperature setpoint. The alarm
deviation is settable from 10-100° F and the factory default is 50° F.
Pit
Setpoint
Deviation Alarm
Setpoint
Gives “Hi” Alarm
Gives “Lo” Alarm
Deviation Alarm
Setpoint
P
it
T
e
m
p
e
ra
tu
re
Tim e