Syscompact 2000 M pro
Putting the testing system out of operation
822-175-2
77 / 98
14.2.2 Earthing
DANGER
Dangerous voltage in test object
Danger to life or risk of injury due to electric shock or electric arcs.
Use suitable personal protective equipment against electric shocks
and arcing faults.
Keep a distance of at least 50 cm from the protective earthing cable
of the discharge and earth rod.
1. If not yet connected, connect the earth cable of the protective earthing cable of the
discharge and earth rod to the station earth.
2. Assemble the earth rod: Screw the hook into the handle.
3. Contact the test object with the tip of the earth rod.
4. Immediately after earthing, connect the earthing and short-circuit equipment to the test
object.