Commissioning
Syscompact 2000 M pro
34 / 98
822-175-2
6.3 Preparing the test object terminals
The test object terminals are
the connection point and the far end
of the test object.
1. Disconnect all operating resources that are connected to the test object and are not
designed for the stipulated test voltage.
2. Cordon off all metal parts, e.g. lighting masts at the test object terminals or insulate them
with insulating safety plates.
3. Earth all metal parts at the terminals to avoid dangerous charging.
4. All cables that are used in danger zones can also carry high voltage potential outwards.
Therefore, remove these cables from the danger zone or ensure low-resistive earthing and
short-circuit.
5. Follow the cable line and ensure that no work is being carried out underground on gas
lines and that there are no other danger points.
6.4 Setting up the system
WARNING
Potential differences between the system and the earth possible
Danger to life or risk of injury due to electric shock.
If a cable fault is located near to the system, there may be potential
differences between the system and the earth in surge mode.
Place the system at a distance of several meters to the cable route
or cable fault location.
If operating in ‘surge mode’, cordon off the system at distance of at
least 1.5 m.
During surge mode, people may only stand outside the cordoned off
area.
Before starting surge mode, check the cable route for potential
dangers.
Select the installation location for the system in such a way that
A stable base is guaranteed and the system cannot tip over,
The system is easy to access for the connections and operation.
sufficient safety distances are maintained. In this regard, comply with EN 50110 for
operation of electric systems (EU/EFTA countries) or the relevant standards
applicable in your country.
6.4.1 Placing the system in the road traffic area
When placing the system in the road traffic area:
Wear a high visibility vest so that road users can recognise you better.
Position the system as far away from the moving traffic as possible.
Secure the work place in compliance with the applicable national work safety and accident
prevention regulations as well as local conditions.