Commissioning
Syscompact 2000 M pro
38 / 98
822-175-2
6.6.2 Connecting
Prerequisites
The workplace must be disconnected from the power supply.
Further information: Chapter
Ensuring there is no voltage at the work place
(on page 33)
The connection points and far end are prepared for the measurement.
Further information: Chapter
Preparing the test object terminals
(on page 34)
For measurements on live cables: Chapter
TDR measurement on live cables
(on page 15)
The IRG 2000 is used as an independent device.
Further information: Chapter
Using the IRG 2000 as an independent device
(on page 42)
Connection diagrams
Screened cable with 3 phases (on page 38)
Screened cable with 1 phase (on page 38)
Unscreened cable with 3 phases (on page 39)
Procedure
1. Connect the black terminal of the TDR connection cable to the phase to be tested.
2. Connect the blue terminal of the TDR connection cable to the station earth.
Screened cable with 3 phases
Screened cable with 1 phase