Syscompact 2000 M pro
Putting the testing system out of operation
822-175-2
75 / 98
14.1 Safety instructions for decommissioning
DANGER
Dangerous voltage in test object.
Danger to life or risk of injury due to electric shock.
Before touching the test object, discharge, earth and short it: at the
connection point and at the far end.
You may touch the parts that were under voltage only if they are
visibly earthed and short-circuited.
Disconnect the earth connections as the last connection of the test
setup.
Never disconnect the earth connections as long as power and other
periphery connections are still connected.
14 P
UTTING THE TESTING SYSTEM OUT OF OPERATION