Syscompact 2000 M pro
Acoustic pin-pointing
822-175-2
73 / 98
13.3 Performing acoustic pin-pointing
13.3.1 Safety instructions for the system’s surge mode
WARNING
Potential differences between the system and the earth possible
Danger to life or risk of injury due to electric shock.
If a cable fault is located near to the system, there may be potential
differences between the system and the earth in surge mode.
Place the system at a distance of several meters to the cable route
or cable fault location.
If operating in ‘surge mode’, cordon off the system at distance of at
least 1.5 m.
During surge mode, people may only stand outside the cordoned off
area.
Before starting surge mode, check the cable route for potential
dangers.
13.3.2 Prerequisites
The test area is secured.
The test object is connected properly.
Further information: Chapter
Commissioning
(on page 33)
The parameters for the acoustic pin-pointing have been set.
Further information: Chapter
Setting parameters for the acoustic pin-pointing
(on page 72)
Required devices: Signal receiver (UL 30 universal receiver), BM 30 ground microphone
Follow the user manual of the signal receiver.
If you are performing the measurement with the BAUR UL 30
universal receiver, follow the user manual for the BAUR Locator Set.