Syscompact 2000 M pro
Cable fault pre-location
822-175-2
67 / 98
5. Depending on the intended output voltage, select a voltage range:
Voltage range 0 – 8 kV: Select the
symbol (parallel connection).
With parallel connection, at 8 kV you receive the max. surge energy of 1024 J in the
surge voltage range.
Voltage range 0 – 16 kV: Select the
symbol (series connection).
With series connection, at 16 kV you receive the max. surge energy of 1024 J in the
surge voltage range.
6. Press the
ENTER
key.
The parameters are saved.
12.5.3 Performing ICM measurements
Prerequisites
The test area is secured.
The test object is connected properly.
Further information: Chapter
Commissioning
(on page 33)
The anticipated fault distance is > 150 m.
The IRG 2000 is connected to the system via the
ICM
port.
The general pre-location parameters and the ICM parameters have been set.
Further information: Chapter
Setting the general pre-location parameters on the IRG 2000
(on page 52),
chapter
Setting ICM parameters
(on page 66)
Procedure
1
System control panel
2
IRG 2000 time domain reflectometer
On the system control panel
1. Press the
MENU
key on the display.
2. Select the
SURGE MODE
menu item and press the
ENTER
key.
3. Release the high voltage: Press the
key for at least one second.
The system status changes to the
Ready to switch on
operating state. The red indicator
light flashes for approx. 6 seconds.
4. Switch on the high voltage by pressing the
key within 6 seconds (while the red
indicator light flashes).
The system status changes to the
In operation
operating state. The set parameters appear
on the display.