www.balluff.com
23
english
9
Adjust with the calibration device (continued)
Displayed values (example)
At 0…10 V
At 4...20 mA
Set end point
►
Bring magnet to the new end point.
9.89 V
19.13 mA
►
Hold down
for at least 2 s.
> 2 s
2
⇒
The new end point is set with the last
valid end value.
10.00 V
20.00 mA
Adjust end value
►
The end value can be changed using
and
1)
. The
gradient of the curve changes
(see page 20).
10.00 V
20.00 mA
8.00 V
16.80 mA
►
End calibration procedure: Briefly press
and
simultaneously (< 1 s).
⇒
Set position value is saved.
< 1 s
1
2
8.00 V
16.80 mA
End adjustment
►
Briefly press
and
simultaneously (< 1 s).
< 1 s
1
2
⇒
The current position value is displayed once the
buttons are released.
Any of the individual steps for settings can be
selected. The adjustment process can be
ended at any time.
1
2
1
2
1
= blue button
2
= gray button
BTL7-A/E501-M_ _ _ _-J-DEXC-TA12
Magnetostrictive Linear Position Sensor – Rod Style
Type of protection “db” and “ta”
Flameproof enclosure
Summary of Contents for BTL7-A/E501-M Series
Page 2: ...www balluff com...
Page 4: ...www balluff com...
Page 34: ......
Page 36: ...www balluff com...
Page 66: ......
Page 68: ...www balluff com...
Page 98: ......
Page 100: ...www balluff com...
Page 130: ......
Page 132: ...www balluff com...
Page 162: ......
Page 164: ...www balluff com...
Page 178: ...16 5 1 1 2 3 BTL 5 2 BTL BTL 5 BTL7 A E501 M_ _ _ _ J DEXC TA12 db ta...
Page 182: ...20 7 7 3 2 22 1 1 2 1 2 24 7 3 7 4 7 3 3 25 BTL BTL7 A E501 M_ _ _ _ J DEXC TA12 db ta...