24
english
9
Adjust with the calibration device (continued)
Switch the output to be adjusted (optional)
As standard, the values are adjusted at output 1
and the values at output 2 are inverted
accordingly.
The adjustment can be switched from output 1
to output 2.
Displayed values (example)
At 0…10 V
At 4...20 mA
Initial situation:
– BTL with magnet in measuring range
5.39 V
9.15 mA
Activate adjusting
►
Hold down
for at least 4 s.
> 4 s
2
5.39 V
9.15 mA
Switch the output to be adjusted
►
Hold down
and
for at least 4 s.
> 4 s
1
2
⇒
The output changes with each switch.
►
Continue with
Set start point
(see page 22).
1
= blue button
2
= gray button
BTL7-A/E501-M_ _ _ _-J-DEXC-TA12
Magnetostrictive Linear Position Sensor – Rod Style
Type of protection “db” and “ta”
Flameproof enclosure