22
english
9
Adjust with the calibration device
NOTICE
Interference in function
Adjustment while the system is running may result in
malfunctions.
►
Stop the system before performing adjustment.
Displayed values (example)
At 0…10 V
At 4...20 mA
Initial situation:
– BTL with magnet in measuring range
5.39 V
9.15 mA
Activate adjusting
►
Hold down
for at least 4 s.
> 4 s
2
5.39 V
9.15 mA
Set start point
►
Bring magnet to the new start point.
1.04 V
4.82 mA
►
Hold down
for at least 2 s.
> 2 s
1
⇒
The new start point is set with the last valid start
value.
0.00 V
4.00 mA
Adjust start value
►
The start value can be changed using
and
1)
.
The gradient of the curve changes
(see page 20).
0.00 V
4.00 mA
2.00 V
7.20 mA
►
End calibration procedure: Briefly press
and
simultaneously (< 1 s).
⇒
Set position value is saved.
< 1 s
1
2
2.00 V
7.20 mA
For setting the end point, adjusting the end value, and ending
adjustment, see page 23.
Any of the individual steps for settings can be
selected. The adjustment process can be
ended at any time.
1
2
1
2
1
= blue button
2
= gray button
BTL7-A/E501-M_ _ _ _-J-DEXC-TA12
Magnetostrictive Linear Position Sensor – Rod Style
Type of protection “db” and “ta”
Flameproof enclosure
Summary of Contents for BTL7-A/E501-M Series
Page 2: ...www balluff com...
Page 4: ...www balluff com...
Page 34: ......
Page 36: ...www balluff com...
Page 66: ......
Page 68: ...www balluff com...
Page 98: ......
Page 100: ...www balluff com...
Page 130: ......
Page 132: ...www balluff com...
Page 162: ......
Page 164: ...www balluff com...
Page 178: ...16 5 1 1 2 3 BTL 5 2 BTL BTL 5 BTL7 A E501 M_ _ _ _ J DEXC TA12 db ta...
Page 182: ...20 7 7 3 2 22 1 1 2 1 2 24 7 3 7 4 7 3 3 25 BTL BTL7 A E501 M_ _ _ _ J DEXC TA12 db ta...