www.balluff.com
19
english
Null point
End point
Output gradient
BTL
Unit
Min. value
Null value
End value
Max. value
Error
value
Rising
(output 1)
BTL7-A…
V
−0.5
0
+10.0
+10.5
+10.5
BTL7-E…
mA
3.6
4.0
20.0
20.4
3.6
Falling
(output 2)
BTL7-A…
V
+10.5
+10.0
0
−0.5
−0.5
BTL7-E…
mA
20.4
20.0
4.0
3.6
3.6
Tab. 7-1: Factory settings value table
7.3
Calibration procedure overview
7.3.1 Teach-in
The detailed procedure for teach-in is described
The factory-set null point and end point are replaced by a
new null point and end point. The null point and end point
can be set separately, the output gradient changes.
Steps
►
Move magnet to the new null position.
►
Read new null point by pressing the buttons.
⇒
The current end point remains the same.
Fig. 7-1:
New null point
Before
After
Falling
Rising
Reading new null point
►
Move magnet to the new end position.
►
Read new end point by pressing the buttons.
⇒
The current null point remains the same.
7
Adjust with the calibration device (continued)
Fig. 7-2:
New end point
Before
After
New measuring length 100%
Reading new end point
►
The curves can be inverted by actuating the button.
⇒
Inverting inverts the curves of both outputs. For
example, a rising curve for output 1 is changed to a
falling curve and a falling curve from output 2 is
changed to a rising curve.
BTL7-A/E501-M_ _ _ _-J-DEXC-TA12
Magnetostrictive Linear Position Sensor – Rod Style
Type of protection “db” and “ta”
Flameproof enclosure
Summary of Contents for BTL7-A/E501-M Series
Page 2: ...www balluff com...
Page 4: ...www balluff com...
Page 34: ......
Page 36: ...www balluff com...
Page 66: ......
Page 68: ...www balluff com...
Page 98: ......
Page 100: ...www balluff com...
Page 130: ......
Page 132: ...www balluff com...
Page 162: ......
Page 164: ...www balluff com...
Page 178: ...16 5 1 1 2 3 BTL 5 2 BTL BTL 5 BTL7 A E501 M_ _ _ _ J DEXC TA12 db ta...
Page 182: ...20 7 7 3 2 22 1 1 2 1 2 24 7 3 7 4 7 3 3 25 BTL BTL7 A E501 M_ _ _ _ J DEXC TA12 db ta...