5. To repeat the tests for negative (reverse) demands, type:
TORQUE(0)=-5
6. This should cause a demand of -5% of maximum output (-0.5 V) to be produced at the
DEMAND0 output. Correspondingly, the Spy window's Velocity display should show a
negative value.
7. To remove the demand and stop the test, type:
STOP(0)
This should cause the demand produced at
the DEMAND0 output to become 0 V.
If it is necessary for the motor to turn in the opposite direction for a positive demand, then the
DACMODE
and
ENCODERMODE
keywords should be used. The
DACMODE
keyword is used to
invert the demand output voltage. The
ENCODERMODE
keyword must then also be used to
reverse the incoming feedback signal, to correspond with the inverted demand output. Note
that if
ENCODERMODE
had already been used to compensate for a reversed encoder count
(as described in step 4. above), it will be necessary to change it back to its original setting to
correspond with the inverted demand output set using
DACMODE
. See the Mint help file for
details of each keyword.