OVERLOAD
Accumulated current
2
X time, OVERLOAD occurs at +5V.
PH 2 CURRENT
Sampled AC phase 2 motor current, 2.5V = zero current, 0V = negative
rated peak current, +5V = positive rated peak current.
PH 3 CURRENT
Sampled AC phase 2 motor current, 2.5V = zero current, 0V = negative
rated peak current, +5V = positive rated peak current.
POSITION
Position within a single revolution. 5V = 1 complete revolution. (The counter
will reset to 0 once every revolution.)
External Trip Input
Terminal J1-16 is available for connection to a normally closed thermostat in all operating modes.
This connection is available for connection to a motor thermostat or overload relay. The thermostat
or overload relay should be a dry contact type with no power available from the contact. If the motor
thermostat or overload relay should ever open the circuit indicating an over-temperature condition,
the control will automatically shut down and give an External Trip fault. In order for the External Trip
to be activated, the External Trip parameter in the programming Protection Block must be set to
"ON".
2-27
INSTALLATION