Standard Run 3 Wire Control Mode
Figure 2-18 Standard Run 3-Wire Connection Diagram
See Appendix C For Recommended Terminal Tightening Torques
NOTE:
FOR 4-20MA INPUT MOVE JUMPER JP1 ON THE MAIN CONTROL BOARD
TO THE LEFT TWO PINS.
J1-8
OPEN disables the control and motor coasts to a stop. CLOSED allows current to
flow in the motor and produce torque.
J1-9
MOMENTARY CLOSED starts motor operation in the Forward direction. In JOG mode
(J1-12 CLOSED), continuous CLOSED jogs motor in the Forward direction.
J1-10
MOMENTARY CLOSED starts motor operation in the Reverse direction. In JOG
mode(J1-12 CLOSED), CONTINUOUS closed JOGS motor in the Reverse direction.
J1-11
When OPEN control removes power from motor and disables. Coasts or brakes to
stop depending on Keypad Stop Mode parameter setting.
J1-12
CLOSED places control in JOG mode, Forward and Reverse run are used to jog the
motor.
J1-13
OPEN selects ACC / DEC / S-CURVE group 1. CLOSED selects group 2.
J1-14
CLOSED selects preset speed #1, (J1-12, will override this), OPEN allows speed
command from Analog input #1 or #2.
J1-15
OPEN to run, CLOSED to reset fault condition.
J1-16
OPEN causes an external trip to be received by control. The control will disable and
display external trip when programmed "on". Factory preset is "off".
2-33
INSTALLATION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
SINE +
SINE –
COSINE –
EXCI
COMMON
SHIELD
NOT USED
A
A
B
B
INDEX
INDEX
NOT USED
COMMON
+24V
OPTO IN POWER
OPTO OUT RETURN #1
OPTO OUT RETURN #2
OPTO OUT RETURN #3
OPTO OUT RETURN #4
ENABLE
FORWARD RUN
REVERSE RUN
STOP
CLOSED = JOG SPEED
ACCEL/DECEL/SELECT
PRESET SPEED #1
FAULT RESET
EXTERNAL TRIP
INPUT COMMON
PROGRAMMABLE 0-5V OUTPUT (FACTORY PRESET: SPEED)
PROGRAMMABLE 0-5V OUTPUT (FACTORY PRESET: CURRENT)
J1
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
0-5VDC OR
0-10VDC OR
4-20 mA
ANALOG GND
ANALOG INPUT 1
POT REFERENCE
ANALOG INPUT +2
ANALOG INPUT -2
ANALOG OUT 1
ANALOG OUT 2
USER COMMON
OPTO OUT #1
OPTO OUT #2
OPTO OUT #3
OPTO OUT #4
5kOhm COMMAND POT
REFER TO POWERING THE
OPTO-ISOLATED OUTPUTS
BOTH CLOSED =
FORWARD
RESOLVER
INPUT
INCREMENTAL
POSITION
OUTPUT
MN723H-10/95 11/28/95 1:10 AM Page 45 (Black plate)
Summary of Contents for 23H Series
Page 11: ...1 8 GENERAL INFORMATION MN723H 10 95 11 28 95 1 07 AM Page 12 Black plate...
Page 83: ...3 30 KEYPAD PROGRAMMING AND OPERATION MN723H 10 95 11 28 95 1 13 AM Page 84 Black plate...
Page 99: ...4 16 DIAGNOSTIC INFO AND TROUBLESHOOTING MN723H 10 95 11 28 95 1 14 AM Page 100 Black plate...
Page 125: ...5 26 APPENDIX G MN723H 10 95 11 28 95 1 21 AM Page 126 Black plate...
Page 126: ...MN723H 10 95 11 28 95 1 21 AM Page 127 Black plate...