8.3.5 DI (Digital In) Terminals
The Digital In terminal is suitable for direct connection to a passive switch. No barrier is required.
Connect only to passive (Un-powered) switch.
Table 5, DI Entity/NIFW Parameters
Uo/Voc
Po
Ca
La
Entity
Parameters
6.5 V
194mW 1 uF
8
mH
8.3.6 24 VDC IN (+) and (-)
The 24 VDC IN circuit is connected thru a Controller output type barrier, for example MTL 728.
Table 6, 24 VDC IN Entity/NIFW Parameters
Vmax
Imax
Ci
Li
Pmax
Entity Parameters 30 VDC 125 mA
7 nF
10 uH
8
8.4 Use in Dust Atmospheres
Dust-tight conduit seal must be used when installed in dust hazard environments.
8.5 Safe Guards for I.S. Barriers
A device which has previously been installed without an approved I.S. barrier must NEVER be used
subsequently in an intrinsically safe system. Installing the device without a barrier can permanently
damage the safety related components in the device making the device unsuitable for use in an
intrinsically safe system.
9 REPAIR
THE FLAME PATHS OF THE EQUIPMENT ARE NOT INTENDED TO BE REPAIRED.
CONSULT THE MANUFACTURER OF REPAIR OF A FLAME PATH JOINT IS NECESSARY.
WARNING: EXPLOSION HAZARD
–
SUBSTITUTION OF COMPONENTS MAY IMPAIR
SUITABILITY FOR USE IN A HAZARDOUS LOCATION
Only Masoneilan qualified ESD service personnel are permitted to make repairs. The only replacement
part offered for the ESD is the display cover. For more information, contact Masoneilan Dresser LLC.
50 Thomas Patten Dr. Randolph MA 02368 USA.
9.1 Cover (display)
Make sure that:
The gasket is seated in the groove in the housing flange.
No wires or retaining cable can be trapped under the cover flange.