Masoneilan SVI II ESD Quick Start Guide
=
|
31
3. Select mounting hole A, B, C or D for the stroke of the valve. For example, hole B is
shown in Figure 9 on page 32 for a size 10 actuator with 1.0" stroke. Unless
otherwise specified, the SVI II ESD mounting assumes that the actuator is in the
normal upright position. The mounting hole in the slotted opening of the mounting
bracket must be left when facing the actuator, with the actuator in the upright
position.
4. Thread the take-off rod to the actuator stem connector. Refer to Figure 8. Ensure
that the travel pointer located on the coupling is correctly positioned.
5. Attach the right hand threaded rod end to the SVI II ESD lever using a 1
⁄
4 - 20 x 1"
cap screw and nut as shown. The lever hole position to be used depends upon the
specific valve stroke. Refer to Figure 9 on page 32 and the Reciprocating Valve
Linkage Selection, Table 3 on page 32.
6. Thread the right hand lock nut and turnbuckle onto the right hand rod end
approximately two turns. Turnbuckle length is a function of actuator size. (Refer to
Table 3.).
7. Secure the magnet housing assembly, including the lever and right hand rod end,
to the bracket using four M5 X 10 mm flat head screws.
8. Attach the left hand threaded rod end to the take-off rod with 1
⁄
4 - 20 UNC nut and
thread the left hand lock nut onto the rod end.
Figure 8 Reciprocating Linkage
9. Move the valve to its closed position. For air to extend, this requires using air
pressure in the actuator to fully stroke the actuator. For air to retract, actuators
vent the actuator of air pressure.
10. Thread the turnbuckle onto the left hand threaded rod end. Refer to Figure 8.
11. Adjust the turnbuckle until the hole in the SVI II ESD lever is aligned with the
indicating hole in the bracket. Tighten both turnbuckle lock nuts. Refer to Figure 7.