© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
94 |
=
BHGE
The maximum voltage that can be applied to the digital switch outputs is 30 VDC. This is an open
circuit parameter (the digital switch is in the open state). Under open circuit conditions, the
switch current will be less than 0.200 mA.
The switch maximum current rating is 1 A. When the switch is ON, the typical switch voltage is
1V.
When the switch is on (closed) the external voltage must be dropped across the load (Figure 24).
Inductive Load, Solenoid, Incandescent Lamp Configuration
Figure 24 Simplified Switch Installation Drawing: Correct Configuration
Consult with qualified personnel to ensure that
electrical requirements for the switch are met.
The load must be designed such that the current in
the circuit is
1 A at all times. Some 3rd party
devices, such as incandescent lamps or solenoids,
require surge and back EMF protection to prevent
voltage spikes.
CAUTION
CAUTION
SVI II ESD Switch Output:
1
V with switch ON
External
Voltage
Source
LOAD
Load is designed to limit current through the switch to < 1 A.
+
-
If the load is inductive (solenoid,
incandescent lamp, etc.), then install a
Freewheel or Flyback diode to prevent
switch damaging EMF voltage spikes.
+
-