© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
Masoneilan SVI II ESD Quick Start Guide
=
|
65
Viewing Configuration Data
To view SVI II ESD configuration data:
1. Access the VIEW DATA menu from the MANUAL menu by pressing the
+
button.
2. Press
*
to examine the configuration.
3. Press
+
to scroll through and observe the factory configuration.
4. Press
+
until
MANPOS
appears.
5. Select with
*
.
When the adjustment screen appears.
6. Stroke the valve open by holding
+
down. The rate of set point change is slow to
begin, but increases speed while the
+
is pressed.
7. Stroke the valve to several values.
8. Verify the action is as desired.
Viewing Status Messages
To view SVI II ESD status messages:
1. Press
+
and
*
to select
VIEW ERR.
2. Observe any internal errors. For example, there should be a RESET status caused
by powering up. If the positioner was powered without air a Position Error or
POSERR
can appear.
3. Press
+
to view all faults.
4. Press
*
to return to
MANual
menu.
5. Press
+
until
CLR ERR
appears.
6. Press
*
CLR ERR
.
WAIT
is displayed for a second or two.
Table 8: VIEWDATA Settings
Configuration
Parameter
Typical Setting
Optional Setting
Air Action
ATO
ATC
Air Pressure Units
PSI
BAR
KPA
Language
ENGLISH
FRENCH, GERMAN, ITALIAN, PORTUGUESE,
SPANISH, JAPANESE (simplified)