© 2018 Baker Hughes, a GE company, LLC. All rights reserved.
Masoneilan SVI II ESD Quick Start Guide
=
|
85
Doc Number ES-727
Revision
W
PDR ECO-
0029774
11/15/2017
Written By
P.Levesque
13DEC2006
Checked
T.Kabir
10JAN2007
Filename
ES-727.DOC
Page 7 of 13
Approved
T. Kabir
10JAN2007
Copyright 2017 as an unpublished trade secret. This document and all information herein is the property of
Dresser LLC.
It is confidential
and must not be made public or copied and is subject to return upon demand.
7.1
Manufacturers Name and Location
Dresser LLC.
12970 Normandy Blvd.
Jacksonville FL 32221 USA
7.2
Summary of Agency Markings
(Factory Mutual)
{Certifying
Agency}
In group a xp installations conduit seal required within 18 inches of enclosure
IS
–
CL I/II/III; DIV 1; GP A, B, C, D, E, F, G
{Intrinsically Safe}
XP
–
CL I; DIV 1; GP A, B, C, D
{Explosionproof}
NI
–
CL I; DIV 2; GP A, B, C, D
{Non-Incendive}
DIP
–
CL II/III; DIV 1; GP E, F, G
{Dust Ignitionproof}
S
–
CL II/III; DIV 2; GP F, G {Special Protection}
{Certifying Agency}
CL I; DIV 1; GP B, C, D
{Explosionproof, gas}
CL II; DIV 1; GP E, F, G
{Explosionproof, dust}
CL III, DIV 1
{Explosionproof, fiber}
IS
–
CL I; DIV 1; GP A, B, C, D
{Intrinsically Safe, gas}
IS
–
CL II; DIV 1; GP E, F, G
{Intrinsically Safe, dust}
IS
–
CL III; DIV 1
{Intrinsically Safe, fiber}
(ATEX)
{CE Conformity Marking, QAN Notified
Body Number}
FM17ATEX0072X
{Certificate Number}
II 1G Ex ia IIC T6..T4 Ga
{Intrinsically Safe, gas}
II 1D Ex ia IIIC T96°C Da
{Intrinsically Safe, dust}
{Explosion Protected Mark}