7. The
Raw Position Sensor
value measured must in accordance with Table 2 on
Figure 10 ValVue ESD for Checking Magnet Position
Checking Actuator, Linkages, or Rotary Adapter
Verify that the mounting has not been damaged in shipment for a pre-mounted SVI II ESD, phys-
ically inspect the actuator, linkage. Record the following information for the configuration check-
out:
Valve Air to Open (ATO) or Air to Close (ATC)
Actuator pressure rating
Actuator bench range
Inherent trim characteristic of the control valve; linear, equal percentage, or
other.
NOTE
For the aforementioned information, refer to the valve data sheet
or model number of control valve.
Verify Mounting and Linkage Adjustment
Inspect the mounting and make any needed adjustments before running the PST Controller and
checking the digital configuration.