Display Cover Removal and Installation
The cover with display (Figure 18) is standard with the SVI II ESD. To replace the display cover, fol-
low the instructions below for removal and installation.
Tools Needed for Cover Replacement
5 mm hex key for the cover
3 mm hex key for the lanyard
Removing the SVI II ESD Display Cover
To remove the SVI II ESD Display cover:
1. Using a 5 mm Hex key unscrew the four screws around the perimeter of the SVI II
ESD cover.
2. Lift the cover off the positioner.
Figure 18 SVI II ESD Pneumatic and Display Covers
Do not remove the instrument cover or connect to
an electrical circuit in a Hazardous Area unless the
power is disconnected.
If natural gas is supplied, natural gas may escape
from the SVI II ESD on removal of the cover or
components.
WARNING
Pneumatic
Cover
Cover
Display