Masoneilan SVI II ESD Quick Start Guide
=
|
47
7. Turn on the voltage source. On initial power up of a newly installed SVI II ESD, the
positioner runs in
SETUP
mode using the default factory-installed instrument
parameters. Once calibrated and configured and set to
NORMAL
, the positioner
cycles through the
NORMAL
cycle menu and the following values appear:
PRES
: Pressure - unit of measurement and value
SIGNAL
POS
(Position)
An exclamation point (
!
) appears in the display’s top left corner to indicate
that further instrument status is available.
8. Proceed to“Configuration” on page 62 and “Calibration” on page 66.
NOTE
The safety function of the SIF (shutdown of the valve on demand)
must be tested after installation.