INICT03 INFI-NET TO COMPUTER TRANSFER MODULE
INTRODUCTION
I-E96-401A
E - 3
Table E-4. INICT03 Dipswitch LLB3 SCSI Port Settings
Position
Setting
Function
1
0
SCSI port disabled.
1
SCSI port enabled.
2/3/4
0/0/0
Address = 0.
0/0/1
Address = 1.
0/1/0
Address = 2.
0/1/1
Address = 3.
1/0/0
Address = 4.
1/0/1
Address = 5.
1/1/0
Address = 6.
1/1/1
Address = 7.
5
0
SCSI parity checking disabled.
1
SCSI parity checking enabled.
6/7/8
1
Not used.
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF.
Table E-5. INICT03 Jumpers J1, J2, J4 and J5 Settings
Jumper
Setting
Function
J1
1
Vertical
Sets the RS-232-C diagnostic port to oper-
ate as DCE.
Horizontal
Sets the RS-232-C diagnostic port to oper-
ate as DTE.
J2
4-3
1 Mbit SRAM device (128k x 8).
4-2
2 Mbits SRAM device (256k x 8).
4-1
4 Mbits SRAM device (512k x 8).
J4
Open
MFT disable jumper. This jumper must
remain open for normal operation.
J5
30 V
Disconnects Controlway for operation in
MMUs that have -30 VDC (early Network
90).
MODB
Connects Controlway channel B for opera-
tion in MMUs that have Controlway (INFI
90).
NOTE:
1.This feature is used by Bailey service personnel. The J1 setting does not affect the module during
normal operation.
Summary of Contents for infi 90 NIMP01
Page 2: ......