INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 10
I-E96-401A
®
RS-232-C COMMUNICATION CABLE
The RS-232-C communication cable connects the IMP module
to a computer, terminal, printer or modem (Figure
). Table
lists the requirements of the RS-232-C cable, its applica-
tion, connector assignments and length restrictions. To install
the RS-232-C cable:
1. Turn off power to the host computer or terminal.
2. Install the RS-232-C cable to the DB-9 connector on the
IMP module marked P5 for port 1. Connect the other end of the
RS-232-C cable to the external device.
3. Install the RS-232-C cable to the DB-9 connector on the
IMP module marked P6 for port 2. Connect the other end of the
RS-232-C cable to the external device.
RIBBON CABLE 6634408A2
This cable connects the NIMP01 and NIMP02 termination mod-
ules for redundant module configuration. To install the cable:
1. Insert one end of the cable into the P1 connector of the
NIMP01 termination module.
2. Insert the other end of the cable into the P10 connector of
the NIMP02 termination module.
3. Insert one end of the cable into the P11 connector of the
NIMP01 termination module.
4. Insert the other end of the cable into the P9 connector of
the NIMP02 termination module.
Table 2-1. IMP Cable Applications, Connections and Length Requirements
Cable
Connections
Maximum Length
Meters (Feet)
From
To
Device
Connector
Device
Connector
HCBL01
DCE or DTE
device
DB-25
NIMP01
P2 or P3
15 (50)
1
NKTM01
NIMP01
P1
Primary module
P3
30 (100)
NIMP02
Redundant
module
NKTU02 or
NKTU12
NIMP01
P1
Primary module
P3
61 (200)
NIMP02
Redundant
module
6634408A2
NIMP01
P1
NIMP02
P10
30 (100)
NIMP01
P11
NIMP02
P9
NOTE:
1.The specified maximum length only applies to the HCBL01 cable. The performance of INFI 90 modules does not place a restriction on
the maximum length of the RS-232-C cable. Follow industry-wide accepted RS-232-C practices and rules when selecting a suitable
RS-232-C cable for your system.