IMMFP01 AND IMMFP02 MULTI-FUNCTION PROCESSOR
INTRODUCTION
A - 2
I-E96-401A
®
Table A-1. IMMFP01/02 Dipswitch SW3
Module Address Settings
Address
Example
Dipswitch Position
(Binary Value)
1
(128)
2
(64)
3
(32)
4
(16)
5
(8)
6
(4)
7
(2)
8
(1)
7
Y
0
X
0
0
1
1
1
15
Y
0
X
0
1
1
1
1
31
Y
0
X
1
1
1
1
1
NOTES:
0 = CLOSED or ON, 1 = OPEN or OFF.
1 Y = 0 for normal operation, 1 for special operations (Table
2.X = 0 for Controlway (1 Mbaud), 1 for module bus (83.3 kbaud).
3.Position 2 is reserved. Do not change the setting.
Table A-2. IMMFP01/02 Dipswitch SW4 Option Settings
Position Setting
Function
1
0
Perform special operations.
1
Inhibit special operations. Refer to Table
2
0
Inhibit on-line configuration.
1
Perform on-line configuration.
3
0
Perform NVRAM checksum routine.
1
Inhibit NVRAM checksum routine. This setting is used by development personnel and
should never be used for normal operation. The checksum provides additional module
integrity and should be used whenever the module is controlling a process.
4
0
Perform ROM checksum routine.
1
Inhibit ROM checksum routine. This setting is used by development personnel and
should never be used for normal operation. The checksum provides additional module
integrity and should be used whenever the module is controlling a process.
5
0
Reserved for future use.
6
0
Normal.
1
Compact configuration. Moves configured blocks to the top of NVRAM which moves free
space to the bottom (this is known as compacting). Leave switch OPEN and insert mod-
ule into MMU. When front panel LEDs 1, 2 and 4 are ON, remove the module, put the
switch in the CLOSED position and insert the module. The MFP goes into the configure
mode and compacts the configuration.
Leaving this option enabled causes the configuration to be compacted every time the
module is reset, thereby increasing the start-up time. This increase can be substantial if
the configuration is large. Therefore, do not leave this option enabled longer than neces-
sary.
7
0
Normal.
1
Initialize NVRAM (erase configuration) - leave switch OPEN and insert the module into
the MMU. When front panel LEDs 1, 2 and 4 are ON, remove the module, put the switch
in the CLOSED position and insert the module. The module is now ready to be config-
ured. This switch must be CLOSED for normal operation.
8
0
Primary MFP module.
1
Redundant MFP module. When redundancy is used, positions 1 through 7 on the redun-
dant MFP module are set the same as the primary MFP module. Position 8 is set to 0 for
the primary MFP module and to 1 for the secondary MFP module.
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF.+