INTRODUCTION
I-E96-401A
E - 1
APPENDIX E - INICT03 INFI-NET TO
COMPUTER TRANSFER MODULE
INTRODUCTION
The INICT03 INFI-NET to Computer Transfer Module consists
of one circuit board. The board has four dipswitches and four
jumpers. The dipswitches select module operation options,
serial port communication characteristics and the baud rate.
Figure
shows the dipswitch locations. Tables
through
describe the various dipswitches and jumpers.
Figure E-1. INICT03 Module CPU Board Layout
Table E-1. INICT03 Dipswitch UUB0 Options Settings
Position
Setting
Function
1
0
ROM checksumming enabled.
1
ROM checksumming disabled.
2/3
0/0
8 data bits, 1 stop bit, no parity.
0/1
8 data bits, 1 stop bit, even parity.
1/0
8 data bits, 1 stop bit, odd parity.
1/1
8 data bits, 2 stop bits, no parity.
4
0
Port 1 option serial port to host.
1
Port 1 utility option. If this option is selected, port 1 data characteristics are
automatically set to 8 data bits, 1 stop bit, no parity. Otherwise, port 1 data
characteristics are set by dipswitch positions 2 and 3.
5
0
Modem password protection disabled.
1
Modem password protection enabled.
T00200A
CR17
SW6
J4
J1
P5
P4
UUB0
UMB1
LMB2
LLB3
J2
P3
P1
P2
2MBIT
1MBIT
4MBIT
OPTION
SWITCH
SW4
SCSI
SWITCH
SW3
BAUD
RATE
SWITCH
SW1
DIAGNOSTICS
SWITCH
SW2
1 2 3 4
OPEN
5 6 7 8
1 2 3 4
OPEN
5 6 7 8
1 2 3 4
OPEN
5 6 7 8
1 2 3 4
OPEN
5 6 7 8
HW SETUP
1
16
2
15
3
14
4
13
5
12
6
11
7
10
8
9
30V
MODB
J5
Summary of Contents for infi 90 NIMP01