INICT03 INFI-NET TO COMPUTER TRANSFER MODULE
INTRODUCTION
E - 2
I-E96-401A
®
6
0
Port addressing mode disabled.
1
Port addressing mode enabled. When this option is enabled, the ICT module
will expect all commands from the host to send the port address configured
through the UTILITIES as the first character of each command.
7
0
Checksumming option disabled.
1
Checksumming option enabled. When this option is enabled, the ICT module
will expect all commands from the host to include a checksum byte as the last
character before the carriage return. The ICT module includes a checksum in
each reply.
8
0
Not used.
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF.
Table E-2. INICT03 Dipswitch UMB1 Baud Rate Settings
Baud
Rate
Terminal Port
1 Position
Printer Port 2
Position
Baud
Rate
Terminal Port
1 Position
Printer Port 2
Position
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
50.0
0
0
0
0
0
0
0
0
1800.0
0
0
0
1
0
0
0
1
75.0
1
0
0
0
1
0
0
0
2000.0
1
0
0
1
1
0
0
1
110.0
0
1
0
0
0
1
0
0
2400.0
0
1
0
1
0
1
0
1
134.5
1
1
0
0
1
1
0
0
3600.0
1
1
0
1
1
1
0
1
150.0
0
0
1
0
0
0
1
0
4800.0
0
0
1
1
0
0
1
1
300.0
1
0
1
0
1
0
1
0
7200.0
1
0
1
1
1
0
1
1
600.0
0
1
1
0
0
1
1
0
9600.0
0
1
1
1
0
1
1
1
1200.0
1
1
1
0
1
1
1
0
19200.0
1
1
1
1
1
1
1
1
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF.
Table E-1. INICT03 Dipswitch UUB0 Options Settings
(continued)
Position
Setting
Function
Table E-3. INICT03 Dipswitch LMB2 Diagnostics Settings
Position
Setting
Function
1
0
NIS handshake time-out enabled.
1
NIS handshake time-out disabled.
2
0
NIS diagnostic disabled.
1
NIS diagnostic enabled.
3
0
INFI-NET diagnostic utilities disabled.
1
INFI-NET diagnostic utilities enabled.
4
0
Hardware diagnostics disabled.
1
Hardware diagnostics enabled.
5
0
Not used.
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF.