INIIT02 INFI-NET TO INFI-NET TRANSFER MODULE
INTRODUCTION
D - 2
I-E96-401A
®
4
0
Port 2 is a data port.
1
Port 2 is a diagnostic port. If port 2 is con-
nected to a remote INIIT02 (port) module, dis-
connect it before enabling it as a diagnostic
port. Failure of all serial link communication
may result if this precaution is not observed.
5/6
0/0
Diagnostic port baud rate is 1.2 kbaud.
0/1
Diagnostic port baud rate is 2.4 kbaud.
1/0
Diagnostic port baud rate is 9.6 kbaud.
1/1
Diagnostic port baud rate is 19.2 kbaud.
7
0
Do not initialize NVRAM.
1
Initialize NVRAM.
8
0
Not used.
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF.
Table D-2. INIIT02 Dipswitch SW3 Settings
Position
Setting
Function
1
0
Normal operation.
1
Test/diagnostic mode.
2
0
Not used.
3
0
Controlway speed is 1 Mbaud.
1
Module bus speed is 83.3 kbaud.
4
0
Not used.
5
0
NVRAM dump on crash disabled (no dump).
1
NVRAM dump on crash enabled (dump on
crash).
6
0
Both rings on same time base.
1
Separate time bases on rings.
7^
0
No redundant module.
1
Redundant module configured.
8
0
Controlway address 0.
1
Controlway address 1.
NOTE:0 = CLOSED or ON, 1 = OPEN or OFF.
Table D-1. INIIT02 Dipswitch SW4 Options Settings
(continued)
Position
Setting
Function
Summary of Contents for infi 90 NIMP01
Page 2: ......