INSTALLATION
INIIR01 INFI-NET TO INFI-NET REMOTE INTERFACE INSTALLATION
3 - 6
I-E96-607A
®
INNIS01 DIPSWITCH SW4, EVENT AND ERROR COUNTERS
The NIS module can have an I/O expander bus address from
zero to seven. Poles one through three of dipswitch SW4 set the
NIS module address. Refer to Table
for I/O expander bus
address settings. Poles four through eight set the address of
the on-board event and error counters that the NIS module dis-
plays on 16 faceplate LEDs. Table
lists the event
addresses. Table
lists error counter addresses. Assign the
module address, and select an event or error counter and set
dipswitch SW4 accordingly. Keep a record of the dipswitch
SW4 settings in the space provided.
Example of Counter Usage
Counter 09 keeps track of the number of multicast messages received exclud-
ing those originated. To display this counter on the front panel LEDs, set
dipswitch SW4 (Table
) as follows: pole 4 = 0, 5 = 1, 6 = 0, 7 = 0, and 8 = 1.
NOTE: The two INNIS01 modules in an INIIL02 interface must have
different I/O expander bus addresses (set by dipswitch SW4, poles
one through three).
1
0
Toggle group A LEDs if loop 1 is idle or shorted.
Toggle group B LEDs if loop 2 is idle or shorted.
LED display defined by SW4.
1
0
Diagnostic mode.
Normal operating mode.
0
0
0
1
10 Mbaud INFI-NET communication rate.
2 Mbaud INFI-NET communication rate.
1
0
1
1
Do not use.
Do not use.
—
—
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table 3-2. INNIS01 Dipswitch SW3, Loop Mode
(continued)
Pole
1
2
3
4
5
6
7
8
Function
User
Setting
Table 3-3. INNIS01 Dipswitch SW4, I/O Expander Bus Address
Example Settings
Example
Address
Pole
(Binary Value)
1
2
3
4
5
6
7
8
(4)
(2)
(1)
1
0
0
1
x
x
x
x
x
3
0
1
1
x
x
x
x
x
7
1
1
1
x
x
x
x
x
User Settings
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF, x = event/error counter address (refer to Tables
and 3-5).