Table 3-4. INNIS01 Dipswitch SW4, Event Counter Address
Pole
4
5
6
7
8
Hex
Description
User
Setting
0
0
0
0
0
00
Number of timer interrupts.
0
1
0
0
1
09
Number of multicast messages received, excluding origi-
nated messages.
0
1
0
1
0
0A
Number of multicast destinations received.
0
1
0
1
1
0B
Number of time sync messages received, excluding origi-
nated messages.
0
1
1
0
0
0C
Number of broadcast messages received, excluding origi-
nated messages.
0
1
1
0
1
0D
Number of NIS poll messages received, excluding origi-
nated messages.
0
1
1
1
0
0E
Number of NIS poll messages acknowledged (ACK) by this
node.
0
1
1
1
1
0F
Number of NIS poll messages busy negative acknowledged
(NAK) by this node.
1
0
0
0
0
10
Number of messages transmitted, total loop traffic.
1
0
0
0
1
11
Number of messages received and forwarded by this node.
1
0
0
1
0
12
Number of messages originated by this node, including
retries.
1
0
0
1
1
13
Number of message retries originated by this node.
1
0
1
0
0
14
Number of transmitted message watchdog expirations.
1
0
1
0
1
15
Number of messages put into receive buffer and retained.
1
0
1
1
0
16
Number of bytes originated by this node, including retries.
1
0
1
1
1
17
Number of bytes received and forwarded by this node.
1
1
0
0
0
18
Number of I/O expander bus to NIS module handshakes.
1
1
0
0
1
19
Number of I/O expander bus message to transmit buffer
signals.
1
1
0
1
0
1A
Number of I/O expander bus PCU status requests.
1
1
0
1
1
1B
Number of I/O expander bus NIS status requests.
1
1
1
0
0
1C
Number of I/O expander bus interrupts with invalid status.
1
1
1
0
1
1D
Number of transmit buffer realignments due to invalid con-
tents.
1
1
1
1
0
1E
Number of receive buffer realignments.
1
1
1
1
1
1F
Number of status buffer realignments.