INSTALLATION
UNPACKING AND INSPECTION
3 - 2
I-E96-607A
®
UNPACKING AND INSPECTION
1. Examine the hardware immediately to verify that it has not
been damaged in transit.
2. Notify the nearest Bailey Controls Company sales office of
any such damage.
3. File a claim for any damage with the transportation com-
pany that handled the shipment.
4. Use the original packing material and container to store the
hardware.
5. Store the hardware in an environment of good air quality,
free from temperature and moisture extremes.
INIIR01 INFI-NET TO INFI-NET REMOTE INTERFACE INSTALLATION
Install the modules, termination devices and cables that make
up an INIIR01 INFI-NET to INFI-NET Remote Interface. Two
complete interfaces are required, one for each loop. The
required modules are:
•
Two INIIT02 modules, one for each loop.
•
Two INNIS01 modules, one for each loop.
•
Two NTCL01 Communication Termination Units or NICL01
Communication Termination Modules, one for each
INNIS01 module.
•
One termination unit cable or one termination module
cable for each NTCL01 or NICL01 termination device. The
NTCL01 termination unit uses NKLS01 or NKLS11 termi-
nation cables. The NICL01 termination module uses
NKLS02 or NKLS12 termination cables.
•
Two NTMP01 Multi-Function Termination Units or NIMP01
Multi-Function Termination Modules, one for each INIIT02
module.
•
One termination unit cable or one termination module
cable for each NTMP01 or NIMP01 termination device. The
NTMP01 termination unit uses NKTU01 or NKTU11 termi-
nation cables. The NIMP01 termination module uses
NKTU02 or NKTU12 termination cables.
•
One external serial communication link is required such as
a modem or transceiver.
For redundant INFI-NET to INFI-NET remote interfaces, double
the required modules, termination units or modules, cables and