INIIR01 REDUNDANT CONFIGURATIONS
REDUNDANT CONFIGURATIONS
E - 2
I-E96-607A
®
transceiver. If failover occurs, the secondary INIIT02 module
connects the antenna to the redundant transceiver.
Function
Code 202 - INFI-NET to INFI-NET Remote Transfer Module
Executive Block (INIIT02)
in the
Function Code Application
Manual
explains how to configure the executive block when
using redundant transceivers.
Voltage levels and polarities of enable signals to transceivers
and other communications equipment vary. Refer to the appli-
cable user manuals for the operating specifications of trans-
ceivers or other communication equipment before making any
connections to the IMDSO01, IMDSO02, IMDSO03 or
IMDSO04 Digital Slave Output Modules, or IMDSM05 Digital
Slave I/O Module.
Redundant Termination Units/Modules
Redundant configurations can be with or without redundant
termination units or modules. In both cases, one or both serial
ports can be used for data transfer depending on the needs of
the application. Figures
through
show redundant
interfaces using various termination unit and module configu-
rations.
Figure
illustrates redundant INIIT02 modules using a sin-
gle NTMP01 Multi-Function Processor Termination Unit. In
this configuration, the INIIT02 modules share a single termina-
Figure E-1. Control of Redundant Communication Equipment
T00217A
INIIT02
INIIT02 IMDMS05
IMDMS05
PRIMARY
SECONDARY
NKTU01
NKTU01
NKTU01
NKTU01
P1
P1
P1
P3
NTDI01
NTMP01
NTDI01
A1
–
+
A1
–
+
A2
–
+
A2
–
+
A3
–
+
A3
–
+
A4
–
+
A4
–
+
REDUNDANT
TRANSCEIVER
MODEM
PRIMARY
TRANSCEIVER
ANTENNA
SWITCH
SELECT
ENABLE
ENABLE
RS-232-C (LINES 1-5, 8, 20)