OPERATING PROCEDURES
INIIR01 MODES OF OPERATION
4 - 4
I-E96-607A
®
Stop/Reset Switch
Push the stop pushbutton once and wait for the red/green sta-
tus LED to turn red before removing the INIIT02 module from
the module mounting unit. Using the stop pushbutton allows
any NVRAM write in progress to complete before the module
halts operation.
After module operation stops, pushing the stop/reset switch
once more resets the INIIT02 module. This action:
1. Resets the module to power up values after a stop.
2. Recovers from an operator-initiated stop or module
time-out.
NOTE:
Pressing and holding the switch will not stop and reset the
module. It will only stop the module. You must release, then press
again to reset. If the module halts due to an error and the status LED
is red, a single push resets the module.
INIIR01 MODES OF OPERATION
The INFI-NET to INFI-NET remote interface has two modes of
operation: Execute and configure.
Execute Mode
This is the normal mode of operation for the INIIT02 module. In
the execute mode, the INIIT02 module on the central INFI-NET
loop communicates with the INIIT02 module on the remote
INFI-NET loop. They process exception reports, and control
and configuration messages.
Configure Mode
The configure mode allows the executive block configuration to
be modified. While in the configure mode, all INIIT02 module
functions continue to operate normally. Any changes made to
the executive block (function code 202) of the INIIT02 module
have no effect until the module returns to the execute mode.
You must have an INFI 90 operator interface device to do con-
figuration tasks. Refer to the product instruction for your par-
ticular operator interface for details.
INIIT02 EXECUTIVE BLOCK CONFIGURATION
To change INIIT02 executive block specifications, the module
must be in the configure mode. New (changed) specification
values will not become effective until the module is reset or the
module is placed in execute mode. Changing the mode to exe-
cute will cause the module to do a software reset.