INSTALLATION
INIIR01 INFI-NET TO INFI-NET REMOTE INTERFACE INSTALLATION
I-E96-607A
3 - 11
INIIR01 Interface Mounting Unit Preparation
The INIIR01 INFI-NET to INFI-NET Remote Interface requires a
dedicated module mounting unit. If the module mounting unit
is part of an older system, it must be checked for -30 VDC. The
next three subsections explain how to check the module
mounting unit for -30 VDC, INIIT02 module installation
Table 3-7. INIIT02 Dipswitch SW4, Options
Pole
1
1
2
3
4
5
6
7
8
Function
User
Setting
0
1
ROM checksum enabled.
ROM checksum disabled.
0
1
RS-232-C DTE mode (direct connections).
RS-232-C DCE mode (modem connections).
0
1
Equipment select output initially de-energized.
Equipment select output initially energized.
0
1
Enable port 2 as data channel.
2
Enable port 2 as diagnostic channel.
3
0
0
0
1
1200 baud rate on diagnostic port.
2400 baud rate on diagnostic port.
1
0
1
1
9600 baud rate on diagnostic port.
19200 baud rate on diagnostic port.
0
1
Do not initialize NVRAM.
Initialize NVRAM.
0
1
Disable alternate default baud rate.
Enable alternate default baud rate.
4
NOTES:
1. 0 = CLOSED or ON, 1 = OPEN or OFF.
2. If the diagnostic port is not enabled, then port 2 data characteristics and baud rate are taken from the configuration of the INIIT02 executive
block.
3. If port 2 is connected to a remote INIIT02 port, disconnect it before enabling it as a diagnostic port. Failure of all serial link communication
may result if this precaution is not observed. If the diagnostic is enabled, port 2 data characteristics are 8 data bits, 1 stop bit, and no parity.
Port 1 baud rate is selected by poles 5 and 6.
4. If the alternate default baud rate is enabled, and the INIIT02 module NVRAM is initialized (pole 7 =1), then specifications S9 and S10 of
the INIIT02 executive block are set to the baud rate selected by poles 5 and 6.
CAUTION
To avoid potential module damage, evaluate your system for
compatibility prior to module installation. This module uses
connections to the module mounting unit backplane that
served other functions in early Network 90 systems.
ATTENTION
Pour éviter d'endommager des modules, évaluez la compatibil-
ité de votre système avant de les y brancher. L'uage que fait ce
module de certianes connexions au fond de panier du châssis
de montage diffère de l'assignation prévue par le système Net-
work 90 original.