INSTALLATION
INIIR01 INFI-NET TO INFI-NET REMOTE INTERFACE INSTALLATION
I-E96-607A
3 - 3
external serial communication link. Refer to
more information on how to set up redundant remote interfaces.
To install an INFI-NET to INFI-NET remote interface:
1. Set the jumpers on all the termination units or modules.
2. Install all the termination units or modules and their cables.
3. Set the dipswitches and jumpers on the INNIS01 and
INIIT02 modules.
4. Verify that the module mounting unit does not use -30 VDC.
5. Install the INNIS01 and INIIT02 modules.
6. Install and connect the external communication equipment
to the NTMP01 or NIMP01 termination devices.
Termination Unit/Module Configuration and Installation
Configure and install the required termination units or modules
and their cables before installing any of the interface modules.
NTCL01 OR NICL01 INSTALLATION
The INNIS01 module terminates through an NTCL01 Commu-
nication Termination Unit or an NICL01 Communication Ter-
mination Module. These devices terminate the INFI-NET
communication loop through either twinax or coax terminals.
Appendices
contain a quick reference of termination
unit or module jumper settings, board layout and cable con-
nections. Refer to the
Communication Termination Unit
(NTCL01)
instruction or the
Communication Termination
Module (NICL01)
instruction for specific directions on config-
uring jumpers, mounting, termination cable installation, and
twinax/coax cable lengths.
NTMP01 OR NIMP01 INSTALLATION
The INIIT02 module terminates through the NTMP01
Multi-Function Processor Termination Unit or NIMP01
Multi-Function Processor Termination Module. Jumpers select
the RS-232-C signals required for the INIIT02 module to act as
data communication equipment (DCE) or data terminal equip-
ment (DTE). The NTMP01 termination unit provides DB-25
connectors; the NIMP01 termination module provides DB-9
connectors to terminate the remote communication device.
Appendices
contain NTMP01 and NIMP01 jumper con-
figuration information.
explains several ways to
terminate redundant INIIR01 interfaces and provides an exam-
ple of redundant communication equipment setup. Refer to the