INSTALLATION
INIIL02 INFI-NET TO INFI-NET LOCAL INTERFACE INSTALLATION
3 - 18
I-E96-607A
®
NTCL01 or NICL01 Installation
Configure and install the required termination units or modules
and their cables before installing any of the interface modules.
The INNIS01 module terminates through an NTCL01 Commu-
nication Termination Unit or an NICL01 Communication Ter-
mination Module. These devices terminate the INFI-NET
communication loop through either twinax or coax terminals.
Appendices
contain a quick reference of termination
unit or module jumper settings, board layout and cable con-
nections. Refer to the
Communication Termination Unit
(NTCL01)
instruction or the Communication Termination Mod-
ule (NICL01) instruction for specific directions on configuring
jumpers, mounting, termination cable installation, and twi-
nax/coax cable lengths.
INNIS01 Dipswitches and Jumpers
Configure the dipswitches and jumpers on the INNIS01 mod-
ule. Refer to
INNIS01 Dipswitches and Jumpers
for informa-
tion on these dipswitches and jumpers.
NOTE: The INIIL02 interface uses two INNIS01 modules. The two
INNIS01 modules must have different I/O expander bus addresses
(set by dipswitch SW4 on the NIS module).
INIIT03 Dipswitches and Jumpers
The INIIT03 module consists of one circuit board. The circuit
board has four dipswitches, four jumpers and one dipshunt
that set the module operating characteristics and options. Fig-
ure
shows the dipswitch and jumper locations on the
INIIT03 circuit board.
NOTE: Dipswitch positions marked not used or
reserved must be
set to the indicated position, otherwise the INIIT03 module will not
operate properly. Since factory settings may not reflect the default
settings, it is imperative to check all dipswitch and jumper settings
before putting the module into operation.
INIIT03 DIPSWITCH UUB0, MODULE ADDRESS
Dipswitch UUBO sets the INIIT03 module Controlway or mod-
ule bus address, enables module diagnostics and sets its com-
munication rate for Controlway or module bus. Table
explains the function of dipswitch UUBO. Dipswitch poles one
through three set normal operation and communication speed.
Poles four through eight set the INIIT03 module address. The
INIIT03 module must have an address of either zero or one.
NOTE: The preferred setting for position three of dipswitch UUB0 is
Controlway because of its high speed communication and redun-
dancy. In redundant configurations, dipswitch UUB0 should be identi-
cal on the primary and secondary INIIT03 modules, except pole eight.