Installation
MagneW
FLEX+/PLUS+
Electromagnetic Flowmeter Detector
2-37
To install a flanged detector on a PVC pipe using SUS grounding ring material
and a protective plate:
Use this method to install the detector using a protective plate to prevent the PVC
pipe from being deformed or damaged when the bolts are tightened with the specified
torque.
•
Install the protective plate between the outer side of the PVC flange and the
detector, as shown in the figure below. The protective plate protects the PVC
pipe. The torque level for tightening the bolts is not related to the gasket material.
See Table 2-6 on page 2-26 for the appropriate torque.
See Table 2-7 on page 2-31 for the inner diameter of the gasket.
Protective plate
Lining
Grounding ring
Gasket
Figure 2-28 Installation on a PVC pipe using SUS grounding ring material and a
protective plate