Azbil Corporation
Introduction
MagneW
FLEX+/PLUS+
Electromagnetic Flowmeter Detector
1-9
1.3.5: Detector terminal box
The detector terminal box houses the connection terminals used for applying a
standard voltage. Houses the excitation and signal terminals.
WARNING
ELECTRIC SHOCK HAZARD! Turn off power to the converter side before
wiring.
CAUTION
The detector must be grounded (grounding resistance is <100
W
) to avoid output
fluctuation, zero point instability or output drift.
Grounding terminal
Signal terminals
Excitation terminals
Conduit wiring
connectors
Figure 1-8 Detector terminal box main parts
Name
Function
Signal terminals
Marked A, B and C.
Excitation terminals
Marked X and Y.
Conduit wiring
connectors
The excitation cable and the signal cable are wired
through these connectors.
Grounding terminal
This terminal is used to ground the detector (grounding
resistance is <100
W
).