Installation
Azbil Corporation
2-14 MagneW
FLEX+/PLUS+
Electromagnetic Flowmeter Detector
2.4.6: Installation on a vertical pipe
Follow this procedure to install the detector on a horizontal pipe.
Step
Action
Drawing
1
•
Of the flange holes shown by black dots in the
drawing, insert through-bolts into the two holes
at the back and fasten them lightly with nuts.
Slip one centering nut onto each through bolt
before inserting the bolts.
Flange
Terminal
box side
Back
Centering nuts
2
• Turn the detector so that the direction mark on
the detector matches the direction of fluid flow.
• Insert the detector and gaskets between the pipe
flanges.
Gaskets
Direction of
fluid flow
3
•
Insert through-bolts fitted with one centering
nut each into the remaining two flange holes
shown by black dots in steps 1 and 2.
Gaskets
Direction of
fluid flow
4
• Make sure that the detector remains properly
centered.
• Make sure that the gaskets do not protrude
beyond the edges of the pipe flanges.
• When you have checked these items, insert
the remaining through-bolts into the flange
holes and tighten the bolts evenly using the