Azbil Corporation
Installation
MagneW
FLEX+/PLUS+
Electromagnetic Flowmeter Detector
2-25
2.5 :
Installing a flanged detector
CAUTION
Before installing the detector, make sure any foreign matter is flushed from
the interior passage of the detector. Residual foreign matter could cause output
fluctuations.
Do not touch the electrodes or allow oil or fat to come into contact with them to
avoid output fluctuations.
Align the direction mark on the detector in the direction of the liquid flow.
Misalignment can result in a negative output.
The following figure shows the basic installation method for installing a flanged
detector.
Nuts (optional)
Through-bolts (optional)
Pipe
Gasket (Required when
using SUS material
grounding rings.
Otherwise, a gasket is
supplied.)
Figure 2-21
Installing a flanged detector