Installation
Azbil Corporation
2-24 MagneW
FLEX+/PLUS+
Electromagnetic Flowmeter Detector
To install a wafer detector on a PVC pipe using non-SUS grounding ring
material with rubber gaskets and a low fastening torque:
CAUTION
The use of rubber gaskets and a lower fastening torque is not recommended and
can cause insufficient surface pressure between the lining and the grounding ring,
resulting in leakage.
(1) Remove the grounding ring from the detector and insert a rubber gasket 0.5 to 1.0
mm (0.02 to 0.04 inch) thick between the lining and the grounding ring.
(2) Reinsert the grounding ring on top of the rubber gasket.
(3) Remove the PTFE gasket and insert a rubber gasket 3.0 to 4.0 mm (0.12 to 0.16
inch) to replace it.
(4)
With the rubber gaskets in the position shown in the following figure, attach the
detector to the pipe. Both rubber gaskets should be made of the same material.
See Table 2-3 on page 2-11 and Table 2-4 on page 2-11 for the appropriate
dimensions.
Lining
Rubber gasket
3 to 4 mm
(0.12 to 0.16 inch)
Grounding ring
Rubber gasket
0.5 to 1 mm
(0.02 to 0.04 inch)
Figure 2-20 Installation on a PVC pipe using non-SUS grounding ring material
with rubber gaskets
(5) Fasten the bolts with a torque that provides a leakproof joint.