UMAX180800, 20 Thermocouple, 2 RTD, 4 Inputs, 6 Relays Dual CAN Controller
Version 1
Page: 43-71
The J1939 Network setpoints deal with the setpoints such as
ECU Instance Number
and
ECU
Address
. Figure 13 and Table 36 below will explain these setpoints and their ranges.
Figure 13: Screen Capture of Default J1939 Network Setpoints
Table 36: Default J1939 Network Setpoints
Name
Range
Default
Notes
ECU Address
0 to 253
128 (0x80)
Preferred address for a self-
configurable ECU
ECU Instance Number
Drop List
0, #1
– First
Instance
Per J1939-81
4.3.2 RTD Function Block
The RTD Input setpoints are defined in Section 3.5. Refer to that section for detailed information on how these
setpoints are used. The screen capture below displays the available setpoints for each of the RTD Inputs.
Table 37 below highlights the allowable ranges for each setpoint. Due to the same default
settings for each diagnostic, it will be mentioned in the table only once.