Table 46. Default Miscellaneous Setpoints
Name
Range
Default
Notes
Undervoltage Threshold
6.0…36.0
10.0
Units in [Volts]
Overvoltage Threshold
6.0…36.0
30.0
Units in [Volts]
Shutdown Temperature
40…125
75
Units in [Celsius]
CAN1 Diagnostic Message Setting
Drop List
Diagnostics Messages Off
CAN2 Diagnostic Message Setting
Drop List
Diagnostics Messages Off
4.3.12 Diagnostic Setpoints
The Diagnostic setpoints are defined in Section 3.14. Refer to that subsection for detailed
information on how these setpoints are used. The screen capture below in Figure 24 displays
the available setpoints for the Power Supply Diagnostic setpoints. Table 47 below highlights the
allowable ranges for each setpoint.
Figure 24: Screen Capture of Default Diagnostic Setpoints
Table 47. Default Values of Diagnostic Setpoints
Name
Range
Default
Notes
Event Generates a DTC in DM1
Drop List
False
Default changed to
True
for illustration purposes,
Refer to Section 3.14
Event Cleared Only by DM11
Drop List
False
Refer to Section 3.14
Lamp Set by Event in DM1
Drop List
Amber, Warning
Refer to Section 3.14
SPN for Event used in DTC
0...524,287
-
Refer to Section 3.14
FMI for Event used in DTC
Drop List
Voltage Below
Normal, Or Shorted
to Low Source
Refer to Table 30
Delay Before Sending DM1
0…60000
1000
Units in [milliseconds]
4.3.13 Constant Data List Setpoints
The Constant Data List function block is provided to allow the user to select values as desired
for
various logic block functions. The two constants are fully user configurable to any value
b/- 1,000,000. The default values are displayed in the screen capture below.