UMAX180800, 20 Thermocouple, 2 RTD, 4 Inputs, 6 Relays Dual CAN Controller
Version 1
Page: 16-71
Table 5. Controller Signal Sources
Signal
Source
Number
Signal Name
Signal Type
Source Number
0
Not Connected
Undefined
0
1
Universal Input
Discrete or Continuous
1
[1…4]
2
Thermocouple Temperature Input
Any
2
[1…20]
3
Thermocouple Voltage Input
Any
2
[1…20]
4
Thermocouple Input Raw Data
Any
2
[1…20]
5
RTD Temperature Input
Any
2
[1…2]
6
RTD Resistance Input
Any
2
[1…2]
7
RTD Input Raw Data
Any
2
[1…2]
8
CAN Input Signal
Any
2
[1…3]
9
Math Function
Any
2
[1…5]
10
Conditional Logic
Any
2
[1…10]
11
Set-Reset Latch
Any
2
[1…5]
12
Lookup Table
Any
2
[1…10]
13
Programmable Logic
Any
2
[1…3]
14
Global Continuous Constant Signal
Continuous
1
15
Global Discrete Constant Signal
Discrete
1
16
Supply Voltage
Continuous
1
17
Microcontroller Temperature
Continuous
1
1
Depends on the
Input Parameter
.
2
Depends on the
Signal Type
configuration parameter
.
3.3 Universal Inputs
The
Universal Input
function block translates physical input signals into the internal function
block output signal that can be used by other function blocks of the controller.
There are 4 independent
Universal Input
function blocks presenting their own universal
physical inputs.
Figure 4. Universal Input Function Block
The internal function block output signal type and units of measurement are presented below.
Table 6. Universal Input Function Block Output Signal
Input Parameter
Type
Units
Voltage
Continuous
V
Current
Continuous
mA
Discrete Voltage Level
Discrete
{0,1}
Frequency
Continuous
Hz
PWM Duty Cycle
Continuous
%