UMAX030211 Version 1.0.2. Preliminary Documentation – May be subject to change
52 - 85
4.2.11.
1029h Error Behavior
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
1029
0
UINT8
RO
No
6
4
Number of subindexes
1
RW
0-2
1
(no change)
State transition on Comm. fault
2
State transition on DI fault
3
State transition on AI fault
4
State transition on DO fault
5
State transition on AO fault
6
State transition on other faults
4.2.12.
1400h RPDO 1 Communication Parameters
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
1400
0
UINT8
RO
No
4
4
Number of subindexes
1
UINT32 RW
UINT32 0x4000027F COB-ID
2
UINT8
UINT8
0xFF
Transmission type
3
UINT16
UINT16
0
Inhibit time
4
UINT8
UINT8
0
Compatibility entry
5
UINT16
UINT16 0
Event timer
4.2.13.
1401h RPDO 2 Communication Parameters
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
1401
0
UINT8
RO
No
4
4
Number of subindexes
1
UINT32 RW
UINT32 0x4000037F COB-ID
2
UINT8
UINT8
0xFF
Transmission type
3
UINT16
UINT16 0
Inhibit time
4
UINT8
UINT8
0
Compatibility entry
5
UINT16
UINT16
0
Event timer
4.2.14.
1402h RPDO 3 Communication Parameters
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
1402
0
UINT8
RO
No
4
4
Number of subindexes
1
UINT32 RW
UINT32
0xC000047F
COB-ID
2
UINT8
UINT8
0xFF
Transmission type
3
UINT16
UINT16 0
Inhibit time
4
UINT8
UINT8
0
Compatibility entry
5
UINT16
UINT16
0
Event timer
4.2.15.
1403h RPDO 4 Communication Parameters
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
1403
0
UINT8
RO
No
4
4
Number of subindexes
1
UINT32 RW
UINT32
0xC000057F
COB-ID
2
UINT8
UINT8
0xFF
Transmission type
3
UINT16
UINT16
0
Inhibit time
4
UINT8
UINT8
0
Compatibility entry
5
UINT16
UINT16 0
Event timer