UMAX030211 Version 1.0.2. Preliminary Documentation – May be subject to change
58 - 85
4.3.6.
61A0h AI Filter Type
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
61A0
0
UINT8
RO
No
12
12
Number of subindexes
1…12
RW
0-2
0
Input #1 … #12 software filter type
4.3.7.
61A1h AI Filter Constant
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
61A1
0
UINT8
RO
No
12
12
Number of subindexes
1…12
UINT16 RW
1-1000
1
Input #1 … #12 software filter constant
4.3.8.
6302h AO Decimal Digits PV
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
6302
0
UINT8
RO
No
9
9
Number of subindexes
1…9
RW
0-3
0
Output #1 … #9 process value decimal digits
4.3.9.
6310h AO Output Type
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
6310
0
UINT8
RO
No
9
9
Number of subindexes
1…9
UINT16 RW
0, 10, 20
10
Output #1 … #9 type, see Table 11 for details
4.3.10.
6332h AO Decimal Digits FV
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
6332
0
UINT8
RO
No
9
9
Number of subindexes
1…9
RW
0-3
0
Output #1 … #9 field value decimal digits
4.3.1.
6340h AO Fault Mode
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
6340
0
UINT8
RO
No
9
9
Number of subindexes
1…9
RW
0-1
0
0 – no change on fault
1 – apply fault FV on fault (object 7341h)
4.3.2.
6458h PID Physical Unit Timing
Index
Subindex Data
Type
Access
PDO
Mapping
Value
Range
Default
Value
Description
6458
0
UINT8
RO
No
2
2
Number of subindexes
1…2
UINT32
12288
12288
Additional PID controller physical unit timing