Installation,
Wiring,
and
Specifications
2--39
Installation, Wiring, and Specifications
DL105 PLC User Manual, 3rd Edition
The F1--130DA Micro PLC features ten DC inputs and eight AC outputs. The
following diagram shows a typical field wiring example. The AC external power
connection uses three terminals at the top left as shown.
Output Point Wiring
Ground
Neutral
Line
Input Point Wiring
+
--
Optical
Common
Input
+V
Isolator
To other circuits in bank
+
--
Equivalent Circuit,
Standard Inputs (X4 -- X11)
Equivalent Output Circuit
To other circuit in bank
+V
Common
Output
Optical
Isolator/Triac
Derating Chart for AC Outputs
0
2
4
6
8
Points
0
10
20
30
40
50
60
Ambient Temperature (
C/
F)
32
50
68
86
104
122
140
C
F
1.3A
1.2A
1.3A
1.4A
1.5A
1.5A
1.6A
1.7A
1.7A
Fuse
or
C.B.
The ten DC input channels use terminals
on the bottom connector. Inputs are
organized into two banks of four, plus one
bank of two. Each bank has an isolated
common terminal, and may be wired as
sinking or sourcing inputs. The wiring
example above shows all commons
connected together, but separate supplies
and common circuits may be used. The
equivalent circuit for standard inputs is
shown above, and the high-speed input
circuit is shown to the right.
Equivalent Circuit, High-
Speed Inputs (X0 -- X3)
Optical
Common
Input
+V
Isolator
To other circuits in bank
+
--
The eight output channels use terminals on the top connector. Outputs are
organized into four banks of two triac switches. Each bank has a common terminal.
The wiring example above shows all commons connected together, but separate
supplies and common circuits may be used. The equivalent output circuit shows one
channel of a typical bank.
The F1--130DA has a +24V supply output to power external devices. The output is
rated at 0.5 Amperes, and includes short-circuit protection and full isolation from
internal CPU circuitry. These features make it ideal for powering sensors, solenoids,
and other field devices. In fact, it can be used as the DC supply for switches or
F1--130DA
I/O Wiring Diagram
Aux24V
Power Supply
Summary of Contents for DL105
Page 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Page 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Page 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Page 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Page 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...