CPU
S
pecifications
and
Operation
4--4
CPU Specifications and Operation
DL105 PLC User Manual, 3rd Edition
CPU Hardware Setup
CPU Status Indicators
RUN
ON
CPU is in RUN mode
OFF
CPU is in Program mode
FLASHING
CPU is in Upgrade mode
CPU
ON
CPU internal diagnostics
has detected an error.
OFF
CPU is OK.
PWR
ON
CPU power good
OFF
CPU power failure
Communication Port
Com 1 Connects to HPP,
Direct
SOFT,
operator interfaces, etc.
6-pin, RS232C
9600 Baud
Odd parity
Station address fixed (1)
8 data bits
1 start, 1 stop bit
Asynchronous, Half-duplex, DTE
K sequence protocol
Communications
Port
CPU Status Indicators
1
2
3
4
5
6
Cables are available that allow you to quickly
and easily connect a Handheld Programmer or
a personal computer to the DL105 PLCs.
However, if you need to build your own cables,
use the pinout diagrams shown. The DL105
PLCs require an RJ-12 phone plug to fit the
built-in jacks.
The Micro PLC has one built-in RS232C
communication port. The port is generally used
for programming either with the Handheld
Programmer or
Direct
SOFT, and has a fixed
station address of 1. The baud rate is fixed at
9600 baud. This port supports the K--sequence
protocol, which is a proprietary protocol.
Phone Jack
Connector
Port Pinouts
Pin Signal Definition
1
0 V
2
5 V
3
RS232C Data in
4
RS232C Data out
5
5 V
1
2
3
4
5
6
NOTE:
The 5V pins are rated at 200mA maximum, primarilly for use with some
operator interface units.
Communication
Port Pinout
Diagrams
Summary of Contents for DL105
Page 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Page 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Page 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Page 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Page 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...