Standard
RLL
Instructions
5--28
Standard RLL Instructions
Timer, Counter, and Shift Register Instructions
DL105 PLC User Manual, 3rd Edition
T aaa
aaa
T
The Timer instruction is a 0.1 second single
input timer that times to a maximum of
999.9 seconds. The Timer Fast instruction
is a 0.01 second single input timer that
times up to a maximum of 99.99 seconds.
These timers will be enabled if the input
logic is true (on) and will be reset to 0 if the
input logic is false (off).
Instruction Specifications
Timer Reference
(Taaa): Specifies the
timer number.
Preset Value
(Bbbb): Constant value (K)
or a V memory location.
Current Value
: Timer current values are
accessed by referencing the associated V
or T memory location*. For example, the
timer current value for T3 physically
resides in V-memory location V3.
Discrete Status Bit
: The discrete status
bit is referenced by the associated T
memory location. Operating as a “timer
done bit”, it will be on if the current value is
equal to or greater than the preset value.
For example, the discrete status bit for
Timer 2 is TA2.
TMR
B bbb
Preset
Timer #
TMRF
B bbb
Preset
Timer #
The timer discrete status bit and the
current value are not specified in the timer
instruction.
NOTE:
Timer preset constants (K) may be changed by using a handheld
programmer, even when the CPU is in Run Mode. Therefore, a V-memory preset is
required only if the ladder program must change the preset.
Operand Data Type
DL130 Range
A/B
aaa
bbb
Timers
T
0--77
----
V--memory for preset
values
V
----
2000--2377
4000--4177
Constants
(preset only)
K
----
0--9999
Timer discrete status
bits
T/V
0--77 or V41100--41103
Timer current values
V /T*
0--77
NOTE:
* With the HPP, both the Timer discrete status bits and current value are
accessed with the same data reference.
Direct
SOFT uses separate references,
such as “T2” for discrete status bit for Timer T2, and “TA2” for the current value of
Timer T2.
You can perform functions when the timer reaches the specified preset using the
discrete status bit. Or, use comparative contacts to perform functions at different
time intervals, based on one timer. The examples on the following page show these
two methods of programming timers.
Timer (TMR) and
Timer Fast (TMRF)
Summary of Contents for DL105
Page 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Page 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Page 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Page 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Page 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...