CPU
S
pecifications
and
Operation
4--26
CPU Specifications and Operation
DL105 PLC User Manual, 3rd Edition
DL105 System V-memory
The DL105 PLCs reserve several V-memory locations for storing system
parameters or certain types of system data. These memory locations store things
like the error codes, High-Speed I/O data, and other types of system setup
information.
System
V-memory
Description of Contents
Default Values /
Ranges
V2320--V2377
The default location for multiple preset values for the High-Speed Counter
N/A
V7620--V7627
V7620
V7621
V7622
V7623
V7624
V7625
V7626
V7627
Locations for DV--1000 operator interface parameters
Sets the V-memory location that contains the value.
Sets the V-memory location that contains the message.
Sets the total number (1 -- 16) of V-memory locations to be displayed.
Sets the V-memory location that contains the numbers to be displayed.
Sets the V-memory location that contains the character code to be displayed.
Contains the function number that can be assigned to each key.
Powerup operational mode.
Change preset value.
V0 -- V2377
V0 -- V2377
1 -- 16
V0 -- V2377
V0 -- V2377
V-memory location for X,
Y, or C points used.
0, 1, 2, 12, 3
0000 to 9999
V7630
Starting location for the multi--step presets for channel 1. The default value is
2320, which indicates the first value should be obtained from V2320. Since
there are 24 presets available, the default range is V2320 -- V2377. You can
change the starting point if necessary.
Default: V2320
Range: V0 -- V2320
V7631--V7632
Not used
N/A
V7633
Sets the desired function code for the high speed counter, interrupt, pulse
catch, pulse train, and input filter. Location is also used for setting the
power-up in Run Mode option.
Default: 0060
Lower Byte Range:
Range: 10 -- Counter
20 -- Quadrature
30 -- Pulse Out
40 -- Interrupt
50 -- Pulse Catch
60 -- Filtered
discrete In.
Upper Byte Range:
Bits 8 -- 12, 14,15: Unused
Bit 13: Power-up in Run
V7634
X0 Setup Register for High-Speed I/O functions
Default: 1006
V7635
X1 Setup Register for High-Speed I/O functions
Default: 1006
V7636
X2 Setup Register for High-Speed I/O functions
Default: 1006
V7637
X3 Setup Register for High-Speed I/O functions
Default: 1006
System Parameters
and Default Data
Locations
(V Data Type)
Summary of Contents for DL105
Page 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Page 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Page 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Page 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Page 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...